Northeast Extension Sewer (NEES) Contract 2B Branch and Carpenter Road Pumping Station
HRC incorporated two outdoor diesel engine driven generator sets and outdoor paralleling switchgear into the design of the pumping station.
The generators are each rated at 1,750 KW and provide 4,160 volt, 3 phase standby power to individual 320 amp trip generator main breakers located within the paralleling switchgear.
Center Road South Water Booster Station
HRC incorporated an outdoor diesel engine driven generator set into the design of the Booster Station.
The generator is rated at 1,040 KW and provides 480 volt, 3 phase standby power to a 1,600 amp trip generator main breaker located within the main switchboard.
Common Features
Each generator included a base mounted 1800 gallon double wall fuel tank with spill containment at the fill station, high and low fuel level alarms and interstitial tank leak detection alarms.
The generators include a weatherproof, sound attenuated enclosure to provide 85 dBA average sound level at 23 feet.